Motors Are Our Specialty

Located in Dayton, Ohio, M & R Electric Motor Service Inc. is your source for electric motor repair. We specialize in both residential and commercial motors. Our knowledgeable staff can sell you a new motor from our selection of products or perform a full motor repair including installing new bearings, fixing damaged housings and shafts, rewind service, or performing a core loss tests in the worst situations to see if you should repair your motor. Other specialties include:

  • Premium Efficiency Motors
  • AC Inverter Drives & Motors
  • DC Servo Motors
  • Electromagnetic Chucks
  • Farm Duty Motors
  • Gates Belts
  • Laser Alignment
  • Material Hand Motors
  • Motor Balancing
  • Motor Bases
  • Phase Converters
  • Pump Repair
  • Rewind Services
  • Starters & Contactors

Diagnose & Repair Motor Failures

When you are experiencing motor failure and are unsure about how to proceed, let us try to help before you even give us a call. Consult the chart below to easily diagnose many of the most common motor issues and find out how to move forward.

Failure Probable Cause Corrective Measures
Motor Fails to Start
  1. No Voltage Supply
  2. Low Voltage Supply
  3. Wrong Control Connections
  4. Loose Connection at Some Terminal Lug
  5. Overload
  6. Brushes
  1. Check feed connections to control system and from control system to motor.
  2. Check voltage supply and ascertain that voltage remains within 10 percent of the rated voltage shown on the motor nameplate.
  3. Compare connections with the wiring diagram on the motor nameplate.
  4. Tighten all connections.
  5. Try to start motor under no-load conditions. If it starts, there may be an overload condition or a blocking of the starting mechanism. Reduce load to rated load level and increase torque.
  6. Brushes may be worn, dirty, or incorrectly fitted.
High Noise Level
  1. Unbalance
  2. Distorted Shaft
  3. Incorrect Alignment
  4. Uneven Air Gap
  5. Dirt in the Air Gap
  6. Extraneous Matter Stuck between Fan & Motor Casing
  7. Loose Motor Foundation
  8. Worn Bearing
  1. Vibrations can be eliminated by balancing rotor. If load is coupled directly to motor shaft, the load can be unbalanced.
  2. Shaft can be bent, check rotor balance and eccentricity.
  3. Check motor alignment with machine running.
  4.  Check shaft for warping or bearing wear.
  5. Dismantle motor and remove dirt or dust with jet of dry air.
  6. Dismantle motor and clean. Remove trash or debris from motor vicinity.
  7. Tighten all foundation studs. If necessary, realign motor.
  8. Check lubrication. Replace bearing if noise is excessive and continuous.
Overheating of Bearings
  1. Excessive Grease
  2. Excessive Axial or Radial Strain on Belt
  3. Deformed Shaft
  4. Rough Bearing Surface
  5. Loose or Poorly Fitted Motor End Shields
  6. Lack of Grease
  7. Hardened Grease Causing Locking of Balls
  8. Foreign Material in Grease
  1. Remove grease bleeder plug and run motor until excess grease is expelled.
  2. Reduce belt tension.
  3. Have shaft straightened and check rotor balance.
  4. Replace bearings before they damage shaft.
  5. Check end shields for close fit around circumference and tightness.
  6. Add grease to bearing.
  7. Replace bearings.
  8. Flush out housings and re-lubricate.
Intense Bearing Vibration
  1. Unbalanced Rotor
  2. Dirty or Worn Bearing
  3. Bearing Rings Too Tight on Shaft &/or Bearing Housing
  4. Extraneous Solid Particles in Bearing
  1. Balance rotor statically and dynamically.
  2. If bearing rings are in perfect condition, clean and re-lubricate the bearing, otherwise, replace bearing.
  3. Before altering shaft or housing dimensions, it is advisable to ascertain that bearing dimensions correspond to manufacturer’s specification.
  4. Take bearing apart and clean. Reassemble only if rotating and support surfaces are unharmed.
Overheating of Motor
  1. Obstructed Cooling System
  2. Overload
  3. Incorrect Voltages & Frequencies
  4. Frequent Inversion
  5. Rotor Dragging on Stator
  6. Unbalanced Electrical Load (Burnt Fuse, Incorrect Control)
  1. Clean and dry motor; inspect air vents and windings periodically.
  2. Check application, measuring voltage and current under normal running conditions.
  3. Compare values on motor nameplate with those of mains supply. Also check voltage at motor terminals under full load.
  4. Exchange motor for another that meets needs.
  5. Check bearing wear and shaft curvature.
  6. Check for unbalanced voltages or operation under single-phase condition.